PRODUCTS CATEGORIES
	1  Application
	·Thermal-magnetic overload protection
	·Short circuit protection
	·Isolation function
	·Single phase and three phase applications(220V/380V)
	Suitable for industrial, commercial, high-rise and civil residences circuit protection.
	Compliant standard: IEC60898-1
	Features
	·Up to 63A current rating
	·Current limiting design
	·Three levels of short-circuit protection ,categorized by B、C and D curves.
	·Captive screws cannot be lost
	·Contact position indicator(red/green)
	·Easy installation on DIN rail(TH35-7.5)
2. Type designation
	
	3 Technical data
| Specifications | |
| 
					 
						 Rated voltage(v) :  | 
				
					 
						230V~(1P)、400V~(2P/3P/4P)  | 
			
| 
					 
						Rated current(A) :  | 
				
					 
						10、16、20、25、32、40、50、63  | 
			
| 
					 
						Poles :  | 
				
					 
						1P、2P、3P、4P  | 
			
| 
					 
						Rated breaking capacity  | 
				
					 
						6000A  | 
			
| 
					 
						Mechanical life & Electrical life:  | 
				
					 
						6000&4000  | 
			
| 
					 
						Torque(N·m):  | 
				
					 
						3.5  | 
			
| 
					 
						Pollution Degree:  | 
				
					 
						2   | 
			
| 
					 
						 Protection class:  | 
				
					 
						IP20  | 
			
| 
					 
						 Overvoltage category :  | 
				
					 
						Ⅲ  | 
			
| 
					 
						 Tripping characteristics  | 
				
					 
						Table1  | 
			
	Table1: Tripping characteristic (temperature 30℃)
| Model | Tripping Characteristic | Test current | Initial situation | Tripping time | Test result | Remarks | 
| 
				 
					a  | 
			
				 
					B、C、D  | 
			
				 
					1.13ln  | 
			
				 
					Cold  | 
			
				 
					t≤1h  | 
			
				 
					Non-tripping  | 
			
				 
					Current smoothly rises to specified value in 5s  | 
		
| 
				 
					b  | 
			
				 
					B、C、D  | 
			
				 
					1.45ln  | 
			
				 
					Following No.1 test  | 
			
				 
					t≤1h  | 
			
				 
  | 
		|
| 
				 
					c  | 
			
				 
					B、C、D  | 
			
				 
					2.55ln  | 
			
				 
					Cold  | 
			
				 
					1s<t<60s(ln≤32A) 
					1s<t<120s(ln>32A)  | 
			
				 
  | 
		|
| 
				 
					d  | 
			
				 
					B 
					C 
					D  | 
			
				 
					3ln 
					5ln 
					10ln  | 
			
				 
					Cold  | 
			
				 
					t≤0.1s  | 
			
				 
					Non-tripping  | 
			
				 
					Switch on the power supply by closing the auxiliary switch  | 
		
| 
				 
					e  | 
			
				 
					B 
					C 
					D  | 
			
				 
					5ln 
					10ln 
					20ln  | 
			
				 
					Cold  | 
			
				 
					t≤0.1s  | 
			
				 
					tripping  | 
			
				 
					Switch on the power supply by closing the auxiliary switch  | 
		
	Remark: "cold" means without load before test at the base of the calibration temperature.
4 Dimensions(unit :mm)
	