PRODUCTS CATEGORIES
	1. Application
	·Thermal-magnetic overload protection
	·Short circuit protection
	·Isolation function
	·Single phase and three phase applications(220V/380V)
Suitable for industrial, commercial, high-rise and civil residences circuit protection.
	
2. Type designation
	
	3  Technical data
| Specifications | |
| 
				 
					Rated voltage(v)   | 
			
				 
					230V/400V(1P)、400V(2P、3P、4P)  | 
		
| 
				 
					Rated current(A)   | 
			
				 
					6、10、16、20、25、32、40、50、63  | 
		
| 
				 
					Poles   | 
			
				 
					1P、2P、3P、4P  | 
		
| 
				 
					Rated breaking capacity(A)  | 
			
				 
					Table 1  | 
		
| 
				 
					Tripping characteristic  | 
			
				 
					Table 2  | 
		
| 
				 
					Mechanical life  | 
			
				 
					10000  | 
		
| 
				 
					Nominal cross section area (mm2)  | 
			
				 
					Table 3    | 
		
| 
				 
					Tightening torque (N·m)  | 
			
				 
					2.5  | 
		
| 
				 
					Pollution Degree  | 
			
				 
					2   | 
		
| 
				 
					Protection class  | 
			
				 
					IP20  | 
		
| 
				 
					Overvoltage category   | 
			
				 
					Ⅱ  | 
		
	Table 1:  Rated breaking capacity
| Tripping Characteristics | Rated current(A) | Rated breaking capacity(A) | Power factor | 
| 
				 
					B、C   | 
			
				 
					≤40  | 
			
				 
					6000        | 
			
				 
					0.65-0.70  | 
		
| 
				 
					B、C  | 
			
				 
					>40  | 
			
				 
					4500  | 
			
				 
					0.75-0.80  | 
		
| 
				 
					D  | 
			
				 
					≤63  | 
			
				 
					4500  | 
			
				 
					0.75-0.80  | 
		
	Table 2:  Tripping characteristic  (temperature 30℃) 
| Model | Rated current(A) | Initial situation | Test current | Tripping time | Test result | Remarks | 
| 
				 
					Delay  | 
			
				 
					≤63  | 
			
				 
					Cold  | 
			
				 
					1.13In  | 
			
				 
					≤1h  | 
			
				 
					Non-tripping       | 
			
				 
  | 
		
| 
				 
					Delay  | 
			
				 
					≤63  | 
			
				 
					Following No.1 test  | 
			
				 
					1.45In  | 
			
				 
					<1h  | 
			
				 
					tripping  | 
			
				 
					Current  smoothly rises to specified value in 5s  | 
		
| 
				 
					Delay  | 
			
				 
					≤32  | 
			
				 
					Cold  | 
			
				 
					2.55In  | 
			
				 
					1<t<60s  | 
			
				 
					tripping  | 
			
				 
  | 
		
| 
				 
					Delay  | 
			
				 
					>32  | 
			
				 
					Cold  | 
			
				 
					2.55In  | 
			
				 
					1<t<120s  | 
			
				 
					tripping  | 
			
				 
  | 
		
| 
				 
					Instant  | 
			
				 
					Any value  | 
			
				 
					Cold  | 
			
				 
					3、5、10In  | 
			
				 
					≤0.1s  | 
			
				 
					Non-tripping  | 
			
				 
					B、C、D   | 
		
| 
				 
					Instant  | 
			
				 
					Any value  | 
			
				 
					Cold  | 
			
				 
					5、10、20In  | 
			
				 
					<0.1s  | 
			
				 
					tripping  | 
			
				 
					B、C、D   | 
		
	Table 3:  Normal  cross  section  area: ≤16mm² 
| Rated current(A) | Nominal cross section area (mm²) | 
| 
					 
						In≤6  | 
				
					 
						1  | 
			
| 
					 
						6≤In≤13  | 
				
					 
						1.5  | 
			
| 
					 
						13<In≤20  | 
				
					 
						2.5  | 
			
| 
					 
						20<In≤25  | 
				
					 
						4  | 
			
| 
					 
						25<In≤32  | 
				
					 
						6  | 
			
| 
					 
						32<In≤50  | 
				
					 
						10  | 
			
| 
					 
						50<In≤63  | 
				
					 16  | 
			
Table 4 : Installation sizes (mm)
| Poles | a | b | ||
| 
						 
							1P  | 
					
						 
							66±0.64  | 
					
						 
							72±0.64  | 
				||
| 
						 
							2P-4P  | 
					
						 
							69±0.64  | 
					
						 
							75±0.64  | 
				||
	4  Operating conditions.
	4.1 : Ambient  temp. range:-5℃~+40 ℃,average temperature in 24 hours not exceed +35℃
	4.2 : Altitude:≤ 2000m;
	4.3 : At mounting site, relative humidity not exceed 50% at the max temperature of +40 ℃,higher relative humidity is allowable under lower temperature, for example ,RH could be 90% at +20 ℃
	4.4 : Mounting type :  Din rail embedded(TH35-7.5) 
5 Dimensions(unit :mm)
	