PRODUCTS CATEGORIES
	1  Application
	·Thermal-magnetic overload protection
	·Short circuit protection
	·Isolation function
	·High Interruption rating capabilities.
	·Single phase and three phase applications(220V/380V)
Suitable for industrial, commercial, high-rise and civil residences circuit protection.
	
2. Type designation
	
3 Technical data
| Specifications | |
| 
				 
					Rated voltage(v) :  | 
			
				 
					230V(1P)、400V(2~4P)  | 
		
| 
				 
					Rated current(A) :  | 
			
				 
					63A、80A、100A  | 
		
| 
				 
					Poles :   | 
			
				 
					1P、2P、3P、4P  | 
		
| 
				 
					Rated breaking capacity(A ) :  | 
			
				 
					Icu=10000A、Ics=7500A  | 
		
| 
				 
					Rated impulse withstand voltage Uimp(V)  | 
			
				 
					8000V  | 
		
| 
				 
					Tripping characteristics:  | 
			
				 
					Table 1  | 
		
| 
				 
					Mechanical life & Electrical life:  | 
			
				 
					8500&1500(operation frequency:120/h)  | 
		
| 
				 
					Nominal cross section area  
					 (mm2):  | 
			
				 
					Table 2  | 
		
| 
				 
					Pollution Degree :  | 
			
				 
					2   | 
		
| 
				 
					Protection class :  | 
			
				 
					IP20  | 
		
| 
				 
					Overvoltage category :  | 
			
				 
					Ⅱ&Ⅲ  | 
		
Table 1: Tripping characteristics
| Model | Tripping Characteristic | Test current | Tripping time | Test result | Remarks | 
| 
				 
					a  | 
			
				 
					1.05In  | 
			
				 
					Cold 
					Following No.1 test  | 
			
				 
					t≤1h(In≤63A) 
					t≤2h(In≥63A)  | 
			
				 
					Non-tripping  | 
			
				 
  | 
		
| 
				 
  | 
		|||||
| 
				 
					b  | 
			
				 
					1.3In  | 
			
				 
					Cold  | 
			
				 
					t<1h(In≤63A) 
					t<2h(In≥63A)  | 
			
				 
					tripping  | 
			
				 
					Current smoothly rises to specified value in 5s  | 
		
| 
				 
					c  | 
			
				 
					2In  | 
			
				 
					Cold  | 
			
				 
					0<t<300s  | 
			
				 
					tripping  | 
			
				 
  | 
		
| 
				 
					d  | 
			
				 
					8In  | 
			
				 
					Cold  | 
			
				 
					t≤0.2s  | 
			
				 
					Non-tripping  | 
			
				 
					Switch on the power supply by closing the auxiliary switch 
  | 
		
| 
				 
					e  | 
			
				 
					12In  | 
			
				 
					Cold  | 
			
				 
					t<0.2s  | 
			
				 
					tripping  | 
		
	Note: "cold" means without load before test at the base of the calibration temperature.
Table 2: Normal cross section area: ≤35mm²
| Rated current(A) | Nominal cross section area (mm²) | 
| 
					 
						63  | 
				
					 
						16  | 
			
| 
					 
						80  | 
				
					 
						25  | 
			
| 
					 
						100  | 
				
					 
						35  | 
			
	4  Operating conditions.
	4.1 : Ambient  temp. range:-5℃~+40 ℃,average temperature in 24 hours not exceed +35℃
	4.2 : Altitude:≤ 2000m;
	4.3 : At mounting site, relative humidity not exceed 50% at the max temperature of +40 ℃,higher relative humidity is allowable under lower temperature, for example ,RH could be 90% at +20 ℃
	4.4 : Mounting type :  Din rail embedded(TH35-7.5)  
5 Dimensions(unit :mm)
	