PRODUCTS CATEGORIES
1 Application
LEL8 (electromagnetic), RCCB are applying to the circuit of Ac50/60Hz,230V single phase, 400V three phases , a rated current 16 -100A. and adapted for industrial mining enterprise, trade building, commerce and family. Mainly prevent electric fire and personal casualty accident caused by personal electric shock or leakage of electrified wire netting.
Compliant standard :IEC61008-1.
2. Type designation
3 Technical data
Specifications | |
Rated voltage(v) : |
230/400V~ |
Rated current(A) : |
16、25、32、40、63、80、100 |
Rated sensitivity lrn(mA) |
30、100、300 |
Residual non-operating current lrno |
0.5Irn |
Poles : |
2、4 |
Rated residual making and breaking capacity lr m |
1000A |
Model |
|
Max. tripping time |
Table 1 |
Mechanical life & Electrical life: |
1000 |
2000 |
|
Pollution |
3 |
Protection |
IP20 |
Overvoltage |
Ⅲ |
Table 1 Max. tripping time(s)
Type | mA | Irn | 2Irn | 5Irn |
Non delay |
|
0.1 |
0.06 |
0.04 |
4 Operating conditions.
4.1 : Ambient temp. range:-5℃~+40 ℃,average temperature in 24 hours not exceed +35℃
4.2 : Altitude:≤ 2000m;
4.3 : At mounting site, relative humidity not exceed 50% at the max temperature of +40 ℃,higher relative humidity is allowable under lower temperature, for example ,RH could be 90% at +20 ℃
4.4 : Mounting type : Din rail embedded(TH35-7.5)
5. Dimensions (unit:mm)